Product Overview:40.5kV Gas Insulated Switchgear
The40.5kV Gas Insulated Switchgear is a new generation of medium voltage switchgear developed based on the high voltage 126kV GIS product technology and the medium voltage 40.5kV parameter requirements.
Specifications and Parameters:
NO. | project | unit | Parameter values | |
1 | Rated voltage | kV | 40.5 | |
2 | Rated current | A | Feeder current:1250、2000、2500、3150 | |
Maximum current of the main busbar:4000 | ||||
3 |
Rated short-time power frequency withstand voltage (1min, effective value) |
Phase to phase, relative to ground, vacuum fracture | kV | 95 |
isolating fracture | 118 | |||
4 | Rated lightning impulse withstand voltage (peak) | Phase to phase, relative to ground, vacuum fracture | kV | 185 |
isolating fracture | 215 | |||
5 | Rated short circuit breaking current | kA | 31.5 | |
6 |
Rated short-time withstand current/ rated short-circuit duration |
kA/s | 31.5/4 | |
7 | Rated peak withstand current | kA | 82 | |
8 | Rated short-circuit breaking current breaking times | times | ≥20 | |
9 | Heavy breakdown level during capacitive current opening and closing | / | C2 | |
10 | Mechanical lifespan of circuit breaker | times | 10000(M2) | |
11 | Mechanical lifespan of three position switch | times | ≥3000 | |
12 | Mechanical lifespan of faulty grounding switch | times | ≥3000 | |
13 | Fault grounding switch closing ability | times | 2 | |
14 | Annual SF6 leakage rate | % | ≤0.1 | |
15 | Service life | year | ≥40 | |
16 | Loss of operational continuity category | category | LSC2B | |
17 | Rated frequency | Hz | 50/60 |
Product Features:
Fully enclosed, gas insulated structure, eliminating problems such as condensation, insulation degradation discharge, and contact heating in air insulated switchgear;
Three position isolation switch, equipped with electric mechanism and one key sequential control function. Eliminate the risks of jamming, tipping and injuring people during the operation of the switchgear handcart;
Especially suitable for the renovation of old air cabinets, without the need to redo the foundation, replace cables, or shut down the entire station;
Equipped with self powered SF6 circuit breakers, capable of cutting reactive loads without current interruption, and possessing a C2 level back-to-back capacitor bank disconnection report from Xigao Institute;
Maintain the operating habits of switchgear products, and operation and maintenance personnel can quickly adapt to the use of new products;
In line with the trend of green environmental protection, we provide solutions for mixed gas products;
We can provide SF6/N2 mixed gas environmental protection solutions.