Specifications and Parameters:
No. |
Construction |
Requirement |
1 |
Conductor |
Class 2 compacted plain annealed copper conductor |
2 |
Insulation |
XLPE |
3 |
Filler |
PP yarn |
4 |
Binder |
Suitable tape |
5 |
Outer sheath |
PVC/ST2 Black |
Core identification: color recognition |
Cable marking: by ink-jet printing or laser printing |
e.g.: To be confirmed after order |
Item |
Standard |
Cable design |
IEC 60502-1-2021 |
Conductor |
IEC 60228 |
Insulating and sheathing material |
IEC 60502-1-2021 |
Item |
Standard |
Conductor operating temperature |
0℃~90℃ |
Conductor short-circuit operating temperature |
250 ℃ |
No. of cores & CSA |
Approx. diameter of conductor |
Nominal thickness of insulation |
Filler |
Nominal thickness of outer sheath |
Approx. O.D. of weight cable |
Approx. weight of cable |
mm |
mm |
/ |
mm |
mm |
Kg/km |
|
3×2.5 |
2.04 |
0.7 |
PP yard |
1.8 |
11.1 |
182.2 |
No. of cores & CSA |
Max. DC resistance of conductor at 20℃ |
Max. AC resistance of conductor at 90℃ |
Fault current capacity of conductor (1s) |
Max. allowable pulling force of conductor |
Min. bending radius |
|
During installation |
After installation |
|||||
Ω/km |
Ω/km |
kA |
kN |
mm |
mm |
|
3×2.5 |
1.9 |
9.448 |
0.358 |
525 |
166.5 |
133.2 |